ATV320U30N4B Schneider Variable speed drive, Altivar Machine ATV320, 3 kW, 380…500 V, 3 phases, book
range of product | n
Altivar Machine ATV320
|
|
---|---|---|
product or component type | n
Variable speed drive
|
|
product specific application | n
Complex machines
|
|
variant | n
Standard version
|
|
mounting mode | n
Cabinet mount
|
|
communication port protocol | n
Modbus serial
nCANopen |
|
option card | n
Communication module, CANopen
nCommunication module, EtherCAT nCommunication module, Profibus DP V1 nCommunication module, Profinet nCommunication module, Ethernet Powerlink nCommunication module, Ethernet/IP nCommunication module, DeviceNet |
|
[Us] rated supply voltage | n
380…500 V – 15…10 %
|
|
nominal output current | n
7.1 A
|
|
motor power kW | n
3.0 kW for heavy duty
|
|
EMC filter | n
Class C2 EMC filter integrated
|
|
IP degree of protection | n
IP20
|
operating position | n
Vertical +/- 10 degree
|
|
---|---|---|
product certifications | n
CE
nATEX nNOM nGOST nEAC nRCM nKC nREACH |
|
marking | n
CE
nATEX nUL nCSA nEAC nRCM |
|
electromagnetic compatibility | n
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
nRadiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 nElectrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 n1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 nConducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 nVoltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
|
environmental class (during operation) | n
Class 3C3 according to IEC 60721-3-3
nClass 3S2 according to IEC 60721-3-3 |
|
maximum acceleration under shock impact (during operation) | n
150 m/s² at 11 ms
|
|
maximum acceleration under vibrational stress (during operation) | n
10 m/s² at 13…200 Hz
|
|
maximum deflection under vibratory load (during operation) | n
1.5 mm at 2…13 Hz
|
|
permitted relative humidity (during operation) | n
Class 3K5 according to EN 60721-3
|
|
volume of cooling air | n
11.3 m3/h
|
|
overvoltage category | n
III
|
|
regulation loop | n
Adjustable PID regulator
|
|
speed accuracy | n
+/- 10 % of nominal slip 0.2 Tn to Tn
|
|
pollution degree | n
2
|
|
ambient air transport temperature | n
-25…70 °C
|
|
ambient air temperature for operation | n
-10…50 °C without derating
n50…60 °C with derating factor |
|
ambient air temperature for storage | n
-25…70 °C
|
Unit Type of Package 1 | n
PCE
|
|
---|---|---|
Number of Units in Package 1 | n
1
|
|
Package 1 Weight | n
2.84 kg
|
|
Package 1 Height | n
9.6 cm
|
|
Package 1 width | n
27.5 cm
|
|
Package 1 Length | n
32.5 cm
|
|
Unit Type of Package 2 | n
P06
|
|
Number of Units in Package 2 | n
20
|
|
Package 2 Weight | n
69.8 kg
|
|
Package 2 Height | n
80 cm
|
|
Package 2 width | n
80 cm
|
|
Package 2 Length | n
60 cm
|
Altivar Machine ATV320
Smart variable speed drive from 0.18 to 15kW (0.25 to 20Hp)
Part of Altivar
Altivar Machine ATV320, a variable speed drive designed for Original Equipment Manufacturers (OEMs) that meets simple and advanced application requirements for 3-phase synchronous and asynchronous motors. The IP21/65/66/UL type offers 4X the protection, embedded safety functions (STO,SS1,SLS,SMS,GDL) and Integrated PLC (Altivar Logic) gives the user the best performance for the investment.
Mounting and Clearance
NOTE: The product overall height dimension, including GV2 adapter and EMC plate mounted, becomes 424 mm (16.7 in.) instead of 325 mm (12.80 in.)
Connections and Schema
Connection diagrams conforming to standards ISO13849 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN 60204-1.
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN 60204-1.
The logic input switch (SW1) is used to adapt the operation of the logic inputs to the technology of the programmable controller outputs.
Switch SW1 set to “Source” position and use of the output power supply for the DIs.
Switch SW1 set to “Source” position and use of an external power supply for the DIs.
Switch SW1 set to “Sink Int” position and use of the output power supply for the DIs.
Switch SW1 set to “Sink Ext” position and use of an external power supply for the DIs.
Performance Curves
Derating curve for the nominal drive current (In) as a function of temperature and switching frequency (SF).